Analisis kualitas top up gas SF6 terhadap kinerja trafo 60 MVA 150KV/20KV di gas insulated substation (GIS) 150KV PLN Abdi Guna Papan
G Gas Insulated Substation (GIS) menggunakan Sulfur Hexafluoride (SF6)sebagai medium isolasi karena kekuatan dielektriknya yang tinggi, stabilitas kimia,dan efisiensi dalam memadamkan busur listrik. Namun, penurunan kualitas SF6,terutama dalam titik embun dan kadar air, dapat menurunkan efektivitas isolasi dankemampuan memadamkan busur api, serta meningkatkan risiko kerusakanperalatan. Top up gas SF6 diperlukan untuk memperbaiki kualitas gas dan menjagakeandalan sistem distribusi listrik. Studi literatur dilakukan untuk mendasari teoripengujian kualitas SF6. Data dikumpulkan menggunakan SF6 Analyzer dan HighVoltage Insulation Tester, kemudian dianalisis secara statistik dengan menghitungmean dan standar deviasi resistansi isolasi sebelum dan sesudah top up. Hasilpenelitian menunjukkan bahwa top up gas SF6 secara signifikan meningkatkankualitas gas dan nilai isolasi belitan trafo. Kadar air turun dari 1272 ppmv menjadi262,59 ppmv, dan titik embun dari 72°C menjadi -30,5°C. Resistansi isolasi ratarata pada kondisi sekunder-tanah meningkat dari 9,69 GΩ menjadi 92,25 GΩ,dengan standar deviasi meningkat dari 1,57 GΩ menjadi 15,21 GΩ. Pada kondisiTertier-Sekunder, resistansi meningkat dari 9,89 GΩ menjadi 13,4 GΩ (1 menit)dan lebih dari 1000 GΩ pada 10 menit, serta IP meningkat dari 1,35 menjadi lebihdari 2. Peningkatan ini menunjukkan perbaikan signifikan dalam kualitas isolasi.
G Gas Insulated Substations (GIS) use Sulfur Hexafluoride (SF6) as theinsulating medium due to its high dielectric strength, chemical stability, andefficiency in extinguishing arcs. However, deterioration of SF6, especially in dewpoint and moisture content, can decrease its insulating effectiveness and arcextinguishing capability and increase the risk of equipment damage. SF6 gas top upis required to improve gas quality and maintain the reliability of the electricitydistribution system. A literature study was conducted to ground the theory of SF6quality testing. Data were collected using SF6 Analyzer and High VoltageInsulation Tester, then statistically analyzed by calculating the mean and standarddeviation of insulation resistance before and after top up. The results showed thatSF6 gas top up significantly improved the gas quality and insulation value of thetransformer windings. The moisture content dropped from 1272 ppmv to 262.59ppmv, and the dew point from 72°C to -30.5°C. The average insulation resistancein the secondary-ground condition increased from 9.69 GΩ to 92.25 GΩ, with thestandard deviation increasing from 1.57 GΩ to 15.21 GΩ. In the TertiarySecondary condition, the resistance increased from 9.89 GΩ to 13.4 GΩ (1 min)and more than 1000 GΩ at 10 min, and the IP increased from 1.35 to more than 2.These improvements indicate significant improvements in insulation quality